openclaw skills install @voronindenis5/clean-air-room-plannerUse when buying or placing an air purifier, living through wildfire smoke, pollen season, or construction dust — computes the exact HEPA CADR a room needs from volume, desired air changes per hour (5 ACH smoke, 4-5 allergy, 2-3 general), checks whether YOUR purifier is adequate or where to move it, sizes DIY box-fan filters (CFM from fan curves + MERV pressure drop), runs a pollution diary that correlates indoor PM2.5 with outdoor events, and tells you when to change filters based on real usage hours.
openclaw skills install @voronindenis5/clean-air-room-plannerEvery wildfire season, three mistakes repeat at scale: people buy purifiers too small for their rooms (marketing "large room" claims assume only 2 air changes per hour), they run them on quiet mode (CADR drops 3–5×), and they put them in the wrong place. The engineering is simple — clean air delivery rate (CADR) must match room volume × desired air changes per hour (ACH) — but the industry makes it hard to do the math.
This skill is that math, plus the operational kit around it:
Don't use for: CO / radon / VOC removal (HEPA does nothing for gases — activated carbon is a different mechanism; the tool says so explicitly), industrial cleanrooms, or medical-grade isolation.
# Size a purifier for a room (metric)
python3 scripts/clean_air.py size --area 20 --ceiling 2.7 --use smoke
# Same in imperial
python3 scripts/clean_air.py size --area 220 --height 9 --unit ft --use smoke
# Is my purifier enough? (rated 300 m³/h CADR)
python3 scripts/clean_air.py check --area 20 --ceiling 2.7 --use smoke --cadr 300
# DIY Corsi-Rosenthal box from a 20" box fan + 4 MERV-13 filters
python3 scripts/clean_air.py crbox --fan-cfm 1800 --filters 4
# Pollution diary
python3 scripts/clean_air.py log add --indoor 45 --outdoor 210 --note "smoke peak"
python3 scripts/clean_air.py log add --indoor 18 --outdoor 190 --purifier on
python3 scripts/clean_air.py log analyze
# Filter life
python3 scripts/clean_air.py filter new --name "Living HEPA" --rated-hours 2000
python3 scripts/clean_air.py filter tick --name "Living HEPA" --hours 8
python3 scripts/clean_air.py filter status
required CADR (m³/h) = room volume (m³) × target ACH
| Situation | Target ACH |
|---|---|
| Wildfire smoke event | 5 |
| Allergy season | 4–5 |
| General air quality | 2–3 |
(ACH conventions from smoke-readiness guidance: 5 ACH keeps PM2.5 at a fraction of outdoor levels with windows closed; higher is better during peaks.)
Buy 1.5–2× the computed CADR if you want to run at low speed (quiet, overnight) — CADR on low is typically 20–35 % of the high-speed rating.
A box fan (1500–2200 CFM free-flow) + 4–5 MERV-13 furnace filters as a cube on the intake side. Measured by academic teams (Corsi, Rosenthal et al., 2020–2022) at 600–900 CFM (1000–1500 m³/h) clean air delivery — beating most $400 commercial units for ~$60 of parts, at higher noise.
Pressure-drop rule of thumb: each MERV-13 filter adds resistance; effective airflow ≈ free-flow CFM × 0.35–0.5 depending on filter count and fan curve. More filter surface area (filters in parallel) = less resistance = more flow.
| PM2.5 µg/m³ | Meaning |
|---|---|
| 0–12 | Good |
| 12–35 | Moderate (sensitive groups take care) |
| 35–55 | Unhealthy for sensitive groups |
| 55–150 | Unhealthy |
| 150–250 | Very unhealthy |
| 250+ | Hazardous |
Indoor/outdoor ratio with windows closed, no filtration: typically 0.5–0.8 of outdoor during heavy smoke. With adequate HEPA at 5 ACH in one sealed room: 0.1–0.2.
HEPA media doesn't "clog" on schedule — it loads with dust. Rated hours (500–3000 h) assume average dust. The tracker uses real run-hours and a smoke-loading multiplier (each heavy smoke week counts ~3×) and schedules replacement before pressure drop kills CADR.
$ python3 scripts/clean_air.py size --area 20 --ceiling 2.7 --use smoke
Room: 54 m³ (20 m² x 2.7 m)
Target: 5 ACH (wildfire smoke)
Required CADR: 270 m³/h (~158 CFM)
buy margin: 400 m³/h to allow quiet-speed operation
$ python3 scripts/clean_air.py check --area 20 --ceiling 2.7 --use smoke --cadr 300
Your purifier: 300 m³/h in 54 m³ room → 5.6 ACH → ADEQUATE for smoke
full air change every ~11 minutes; run on HIGH during peaks.
Conventions from public smoke-readiness guidance (EPA Wildfire Smoke Guide, AHAM CADR definitions) and peer-reviewed Corsi-Rosenthal box measurements. Local conditions vary; use a PM2.5 monitor to verify.