openclaw skills install @zw008/industrial-diagnosticsCross-protocol, READ-ONLY OT troubleshooting via the ot-aiops MCP server. diagnose_dataflow localizes a "no data" break (cannot connect vs stale value vs flatline sensor) across any endpoint's reachable hops; alarm_bad_actors runs ISA-18.2 alarm-flood analysis (rate vs thresholds, Pareto offenders, chattering, standing); tag_health ranks bad-quality/flatline/out-of-range/anomaly offenders; historian_health finds flatline/gaps over a sample series. Use when the task is "why is there no data / why did the dashboard go blank", alarm flooding, bad actors, stuck/flatline tags, or general OT data-quality triage. Not for IT/network/Kubernetes/hypervisor/backup troubleshooting.
openclaw skills install @zw008/industrial-diagnosticsThe cross-protocol intelligence layer of ot-aiops (read-only). Structured JSON outputs are designed for an agent to visualize multi-dimensionally. Preview — diagnoses the layers reachable from this host and accepts injected series for the historian/SCADA tiers it cannot reach.
ethernetip-tap for Rockwell/Allen-Bradley Logix).industrial-analytics.diagnose_dataflow(endpoint?, ref?, freshness_threshold_s=60, series?, flatline_eps?)Probes connect → read(ref) → freshness → variance. Returns
{verdict, diagnosis, recommended_action, hops:[{hop, ok, detail}]} where
verdict ∈ cannot_connect (network/PLC down) · comms_ok_value_unreadable
(wrong address) · comms_ok_bad_quality (sensor/source fault) ·
comms_ok_value_stale (upstream stopped updating) · comms_ok_flatline
(stuck source) · healthy. Works over any protocol (ref = OPC-UA node id /
Modbus address / S7 address / MELSEC device). Pass series (scalars or
{value,timestamp}) for freshness/variance when a historian is out of reach.
alarm_bad_actors(events, window_minutes?, chatter_window_s=60, standing_s=86400, top_n=10)ISA-18.2 over events:[{source, timestamp, priority?, state?}]. Returns
{alarms_per_hour, isa_18_2:{ok_max:6,manageable_max:12,flood_min:30}, flood_verdict, priority_distribution, pareto_sources_for_80pct, top_offenders:[{source,count,share_pct,chattering,standing}], chattering[...], standing[...]}.
tag_health(tags, thresholds?)tags:[{ref, samples:[scalar|{value,good|quality}], warn_high?, alarm_high?, ...}].
Returns {overall, offenders:[{ref, latest, flags, anomaly_count, severity 0..3}]}.
Flags: bad_quality, flatline, out_of_range_warn/alarm, statistical_anomaly
(z-score >3σ and IQR fence).
historian_health(series, gap_threshold_s=60, flatline_eps?)series:[scalar|{value,timestamp,quality|good}] → {bad_quality_count, flatline, gap_count, gaps[...], verdict ('ok'|'degraded'|'gappy'|'flatline'|'bad_tag')}.
diagnose_dataflow(endpoint="line1", ref="ns=2;i=5", freshness_threshold_s=30)
→ {"verdict":"comms_ok_value_stale","diagnosis":"... value is STALE ...", "recommended_action":"Trace upstream ...","hops":[...]}